Please use this identifier to cite or link to this item:
http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9434
Full metadata record
DC Field | Value | Language |
---|---|---|
dc.creator.ID | NERI, M. G. G. | pt_BR |
dc.creator.Lattes | http://lattes.cnpq.br/0270463995062823 | pt_BR |
dc.contributor.advisor1 | COSTA, Edson Guedes da. | - |
dc.contributor.advisor1ID | COSTA, E. G. | pt_BR |
dc.contributor.advisor1Lattes | http://lattes.cnpq.br/3930289115658143 | pt_BR |
dc.contributor.referee1 | NAIDU, Sreeramulu Raghuram. | - |
dc.contributor.referee2 | FREIRE, Raimundo Carlos Silvério. | - |
dc.description.resumo | As falhas em isolamentos elétricos são as principais causas das interrupções no fornecimento de energia elétrica aos diversos consumidores. O desempenho das linhas de transmissão de energia está diretamente relacionado com o desempenho dos seus isoladores. Os isoladores poliméricos começaram a ser utilizados no decênio de 1980, quando surgiu sua primeira versão comercial para linha de transmissão. Desde então, o uso de isoladores poliméricos vem aumentando devido as suas diversas vantagens sobre isoladores de porcelana ou de vidro. Entretanto, seu desempenho em longo prazo não é conhecido, tornando-se difícil avaliar a expectativa de vida do isolador. Atualmente, não existe uma técnica consolidada de monitoramento dos isoladores poliméricos. Foram avaliadas diversas técnicas de inspeção para detectar isoladores defeituosos ou na iminência de falhar. As técnicas avaliadas fazem uso da medição de descargas parciais, em laboratório, da radiação ultravioleta, emitida pelas descargas de corona, e da radiação infravermelha, emitida pelos corpos aquecidos. Isoladores poliméricos com e sem defeitos foram submetidos a ensaios elétricos e térmicos e simulações de campo elétrico. Com o trabalho foi possível a criação de um vasto banco de dados sobre o comportamento dos isoladores poliméricos. Analisando os resultados dos ensaios, para medição de descargas parciais, é possível classificar os defeitos apresentados pelos isoladores como de baixa, média ou alta gravidade. Analisando os resultados das simulações do comportamento do campo elétrico é possível perceber que o campo elétrico nos isoladores defeituosos foi mais intenso que no isolador perfeito. A inspeção de isoladores poliméricos com detectores de corona e infravermelho mostrou-se ser uma promissora técnica para detecção de isoladores defeituosos. | pt_BR |
dc.publisher.country | Brasil | pt_BR |
dc.publisher.department | Centro de Engenharia Elétrica e Informática - CEEI | pt_BR |
dc.publisher.program | PÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICA | pt_BR |
dc.publisher.initials | UFCG | pt_BR |
dc.subject.cnpq | Engenharia Elétrica | - |
dc.title | Avaliação de técnicas de monitoramento de isoladores poliméricos. | pt_BR |
dc.date.issued | 2005-07-07 | - |
dc.description.abstract | Fails in insulates of electrical apparatus are among the main causes of energy interruptions in power systems to its customers. The line transmission performance is directly related with insulates performance. The polymeric insulates has been used since the 1980's when the first commercial version for line transmission was released. Since then, the usage of polymeric insulates has been increasing due to many advantages over the porcelain insulates or the glass one. Nevertheless its long term performance is not known, raising difficulties for evaluating the lifetime expectancy. Nowadays there is no consolidated technique for monitoring polymeric insulates. Several monitoring techniques were evaluated to detected defective or pending defective insulates. The evaluated techniques are partial discharge, UV radiation, IR radiation emitted by heated bodies. Both defective and non-defective polymeric insulates were analyzed in electrical and thermic tests as well in electrical field simulations. Therefore a great data bank of polymeric insulates behavior was raised. Taking into account the results of the tests of partial discharge, is possible to classify the fails of the insulates in low, high and medium seriousness. Analyzing the electrical field simulations, we concluded the electrical field in defective insulates was higher than in non defective ones. The survey of polymeric insulates with corona detector and IR technique has shown good results to detect defective insulates. | pt_BR |
dc.identifier.uri | http://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/9434 | - |
dc.date.accessioned | 2019-11-22T20:28:55Z | - |
dc.date.available | 2019-11-22 | - |
dc.date.available | 2019-11-22T20:28:55Z | - |
dc.type | Dissertação | pt_BR |
dc.subject | Isoladores Elétricos | - |
dc.subject | Isoladores Poliméricos | - |
dc.subject | Monitoramento de Isoladores | - |
dc.subject | Linhas de Transmissão | - |
dc.subject | Detector de Ultravioleta | - |
dc.subject | Termografia | - |
dc.subject | Electrical Insulators | - |
dc.subject | Polymeric Insulators | - |
dc.subject | Insulators Monitoring | - |
dc.subject | Transmission Lines | - |
dc.subject | Ultraviolet Detector | - |
dc.subject | Thermography | - |
dc.rights | Acesso Aberto | pt_BR |
dc.creator | NERI, Max Gleison Gonçalves. | - |
dc.publisher | Universidade Federal de Campina Grande | pt_BR |
dc.language | por | pt_BR |
dc.title.alternative | Evaluation of polymeric insulators monitoring techniques. | pt_BR |
dc.identifier.citation | NERI, Max Gleison Gonçalves. Avaliação de técnicas de monitoramento de isoladores poliméricos. 2005. 73f. (Dissertação) Mestrado em Engenharia Elétrica, Curso de Pós-Graduação em Engenharia Elétrica, Centro de Ciências e Tecnologia, Universidade Federal da Paraíba – Campus II - Campina Grande - Paraíba - Brasil, 2005. | pt_BR |
Appears in Collections: | Mestrado em Engenharia Elétrica. |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
MAX GLEISON GONÇALVES NERI - DISSERTAÇÃO PPGEE 2005.pdf | Max Gleison Gonçalves Neri - Dissertação PPGEE 2005 | 1.46 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.