dc.description.resumoEste trabalho apresenta uma análise paramétrica e sugere uma proposta para determinação de reatâncias para reatores de neutro, utilizados como forma de mitigação da corrente de arco secundário durante faltas monofásicas. Os parâmetros analisados foram o comprimento da li nha de transmissão (LT), nível de compensação reativa shunt e relação entre capacitâncias de sequência positiva e zero c1/c0. Para isso, uma análise de sensibilidade foi conduzida fazendo-se uso do programa ATP (Alternative Transients Program) em um conjunto de 10 LTs. Os valo res de corrente eficaz e pico da tensão de restabelecimento do arco secundário foram coletados durante simulações de faltas monofásicas. Os dados foram utilizados para identificar a influên cia devido à alteração dos parâmetros selecionados. O aumento do comprimento tornou as correntes de arco secundário mais elevadas, sendo este efeito acentuado para os menores níveis de compensação. A compensação reativa teve maior impacto na relação entre as reatâncias de sequência positiva e zero considerada “ótima”, sendo este efeito mais notório nas LTs com uma razão c1/c0 maior. Um procedimento de ajuste de curvas foi utilizado para obter equações que representassem o conjunto de dados. Dois cenários foram considerados: os reatores de neutro com menores reatâncias cujas correntes resultantes se encontravam abaixo de 50 A (reatores “mínimos”) e os reatores cujas aplicações propiciaram os menores picos de tensão e correntes eficazes, denominados reatores “ótimos”. As análises para o caso “ótimo” levaram a um conjunto de equações que permitem a obtenção dos valores dos reatores de neutro para diferentes LTs com base nas capacitâncias, não dependendo do comprimento da LT. As análises para o caso “mínimo” mostraram-se mais complexas, e não foi possível identificar comportamentos entre diferentes LTs que permitissem a formulação de um conjunto único de equações. Por fim, uma metodologia foi proposta e comparada com resultados da literatura, permitindo o atendimento aos critérios normativos para uma maior faixa de compensação reativa.pt_BR
dc.publisher.countryBrasilpt_BR
dc.publisher.departmentCentro de Engenharia Elétrica e Informática - CEEIpt_BR
dc.publisher.programPÓS-GRADUAÇÃO EM ENGENHARIA ELÉTRICApt_BR
dc.publisher.initialsUFCGpt_BR
dc.subject.cnpqEngenharia Elétrica.pt_BR
dc.titleAprimoramento de técnicas de seleção de reatores de neutro em linhas de transmissão.pt_BR
dc.date.issued2023-09-29-
dc.description.abstractThis paper presents a parametric analysis and suggests a proposal for determining reactan ces for neutral reactors used to mitigate secondary arc current during single-phase faults. The parameters analyzed were the length of the transmission line (TL), the level of reactive com pensation shunt, and the ratio between positive and zero sequence capacitances c1/c0. To this end, a sensitivity analysis was conducted using the program ATPDraw (Alternative Transients Program) on a set of 10 TLs. The effective current and the first peak of the transient restoring voltage (TRT) values were collected during simulations of single-phase faults. The data was used to identify the influence of changing the selected parameters. Increasing the length made the secondary arc currents higher, and this effect was more pronounced for the lower compen sation levels. Reactive compensation had a greater impact on the ratio between the positive and zero sequence reactances considered “optimal”, with this effect being more noticeable in TLs with a higher c1/c0 ratio. A curve-fitting procedure was used to obtain equations that represented the data set. Two scenarios were considered: the neutral reactors with the lowest reactances whose resulting currents were below 50 A (“minimum” reactors) and those whose applications provided the lowest TRT peaks and effective currents, called “optimal” reactors. The analyses for the “optimal” case led to a set of equations that allow neutral reactor values to be obtained for different TLs based on capacitances without depending on the length of the TL. The analyses for the “minimum” case proved to be more complex, and it was not possible to identify behaviors between different TLs that would allow a single set of equations to be formulated. Finally, a methodology was proposed and compared with results in the literature, allowing the normative criteria to be met for a wider range of reactive compensation.pt_BR
dc.identifier.urihttp://dspace.sti.ufcg.edu.br:8080/jspui/handle/riufcg/38822-
dc.date.accessioned2024-11-01T20:24:16Z-
dc.date.available2024-11-01-
dc.date.available2024-11-01T20:24:16Z-
dc.typeDissertaçãopt_BR
dc.subjectLinhas de transmissãopt_BR
dc.subjectSistemas elétricospt_BR
dc.subjectCorrente de arco secundáriopt_BR
dc.subjectReator de neutropt_BR
dc.subjectTransmission linespt_BR
dc.subjectElectrical systemspt_BR
dc.subjectSecondary arc currentpt_BR
dc.subjectNeutral reactorpt_BR
dc.rightsAcesso Abertopt_BR
dc.creatorBALBINO, Luan da Silva.-
dc.publisherUniversidade Federal de Campina Grandept_BR
dc.languageporpt_BR
dc.title.alternativeImprovement of techniques for selecting neutral reactors in transmission lines.pt_BR
dc.identifier.citationBALBINO, Luan da Silva. Aprimoramento de técnicas de seleção de reatores de neutro em linhas de transmissão. 2024. 126 f. Dissertação (Mestrado em Engenharia Elétrica) – Programa de Pós-Graduação em Engenharia Elétrica, Centro de Engenharia Elétrica e Informática, Universidade Federal de Campina Grande, Paraíba, Brasil, 2023.pt_BR
Appears in Collections:Mestrado em Engenharia Elétrica.

Files in This Item:
File Description SizeFormat 
LUAN DA SILVA BALBINO - DISSERTAÇÃO (PPGEE) 2023.pdf33.79 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.